UGIANT
UL certificate THW , pvc insulated electrical wire thw/tw electrical wire awg size 14 12 10 8 6 4 2 electrical wire
TW/THW is most often used in general purpose wiring circuits, for machine tool wiring and the internal wiring of appliances. Common applications include control panels, wiring for refrigeration equipment, air-conditioning equipment, control wiring of machine tools, automatic washers, etc. It can be used in dry locations up to 90°C (ampacity is limited to 75°C conductor temperature per NFPA 79); or wet locations or other applicable locations when exposed to oil or coolant at temperatures up to 60°C. Type TEW rating permits use in dry locations up to 105°C; or wet locations or other applicable locations when exposed to oil or coolant at temperatures up to 60°C.
Construction characteristics
Conductor material :copper shall be solid or Class B stranded
Insulation: PVC flame-retardant, moisture- and heat-resistant thermoplastic insulation
Electrical characteristics
Rated Voltage Uo/U (Um) :600 V
Maximum operating voltage: 750V
Test voltage: 2500V
Usage characteristics
Maximum operating temperature 90°C
Minimum operating temperature -15°C
Chemical resistance :Restricted to oil, acid & base
Standard : UL Standard83
General purpose wiring for lighting and power - residential,commercial, industrial buildings in accordance with the National Electrical Code, maximum conductor temperature of 75°C in wet or dry locations,for circuits not exceeding 600 volts
When used as type TW, conductor is suitable for use in wet or dry locations at temperatures rated 60°C.
When used as type THW, conductor is suitable for use in wet or dry locations at temperatures rated 75°C.
When used as type THW2, conductor is suitable for use in wet or dry locations at temperatures rated 95°C.
STANDARDS:
1. Listed by UL as Type THW per Standard 83.
2. All sizes carry the VW-1 flame test designation.
3. Listed by UL as Oil Resistant I.
4. Listed by UL as Sunlight Resistant (250 kcmil and larger, black only)
5. 250 kcmil and larger pass UL and IEEE-383 ribbon burner flame test
and are listed For CT Use.
6. Conforms to Federal Specification J-C-30B.
CONSTRUCTION: Annealed uncoated copper conductor, PVC insulation,surface printed.
Specification Size and Technical Data
|
Size |
No. Of Strands |
Insulation |
Nom. |
NEC |
Approx. Wt. |
|
|
AWG or kcmil |
lbs/1000ft |
|||||
|
Thickness |
Diam. |
Ampacity* |
Copper |
Net |
||
|
Mils |
Inches |
|||||
|
14 |
Solid |
30 |
.13 |
20 |
12 |
19 |
|
12 |
Solid |
30 |
.15 |
25 |
20 |
26 |
|
10 |
Solid |
30 |
.17 |
35 |
31 |
39 |
|
14 |
7 |
30 |
.14 |
20 |
13 |
19 |
|
12 |
7 |
30 |
.16 |
25 |
20 |
28 |
|
10 |
7 |
30 |
.18 |
35 |
32 |
41 |
|
8 |
7 |
45 |
.24 |
50 |
50 |
67 |
|
6 |
7 |
60 |
.30 |
65 |
81 |
105 |
|
4 |
7 |
60 |
.35 |
85 |
129 |
160 |
|
3 |
7 |
60 |
.38 |
100 |
163 |
195 |
|
2 |
7 |
60 |
.41 |
115 |
205 |
245 |
|
1 |
19 |
80 |
.49 |
130 |
258 |
315 |
|
1/0 |
19 |
80 |
.53 |
150 |
326 |
390 |
|
2/0 |
19 |
80 |
.57 |
175 |
411 |
480 |
|
3/0 |
19 |
80 |
.62 |
200 |
518 |
595 |
|
4/0 |
19 |
80 |
.68 |
230 |
653 |
735 |
|
250 |
37 |
95 |
.75 |
255 |
772 |
880 |
|
300 |
37 |
95 |
.81 |
285 |
926 |
1040 |
|
350 |
37 |
95 |
.86 |
310 |
1081 |
1205 |
|
400 |
37 |
95 |
.90 |
335 |
1235 |
1365 |
|
500 |
37 |
95 |
.98 |
380 |
1544 |
1685 |
|
600 |
61 |
110 |
1.09 |
420 |
1853 |
2030 |
|
750 |
61 |
110 |
1.19 |
475 |
2316 |
2510 |
|
1000 |
61 |
110 |
1.34 |
545 |
3088 |
3305 |
- Model Number:
- THW wire
- Type:
- insulated
- Application:
- housing building THW wire
- Conductor Material:
- Copper
- Conductor Type:
- strand or solid THW wire
- Insulation Material:
- PVC
- voltage:
- 600V
- certificate:
- UL THW wire
- standard:
- UL Canadian Standards ICEA/NEMA NFPA
- application:
- building wiring THW wire
- cross section:
- 18AWG-1000KCML
- working temperature:
- 60℃, 75℃ usually 90℃
- free Sample:
- free Sample Available THW wire